RESDAS Renewable Energy Systems Design
Assistant for Storage
General recommendations for selection of charge controllers
-
It is essential to use a charge controller that protects the battery from both
overcharging and deep discharging (by disconnecting the load).
-
It is preferable to use a charge controller with adjustable set points. The
choice of the settings of the charge controller is important for all battery
types and must be chosen in accordance with the specifications of the battery
manufacturer for RE systems. The charge controller should allow the battery to
reach an
equalization voltage from time to time. Some charge controllers
lower the charge voltage after reaching full charge (float
charging). If no recommendations for the battery are given then
following settings should be used.
Default battery voltage set points.
| Battery type => |
Vented / Flooded
V per cell at 25°C |
Sealed / VRLA
V per cell at 25°C |
Bulk/boost charge
2 hours / day |
2.4 |
2.4 |
Equalization
6 hours / month |
2.45 to 2.55 |
2.45 |
Low voltage Disconnect,
for discharge current I10 |
1.80 to 1.85 |
1.80 to 1.85 |
Low voltage Disconnect,
for discharge current 10% of I10 |
1.95 to 2.0 |
1.95 to 2.0 |
| Float charge |
2.35 |
2.30 |
-
If the battery will be operated outside the temperature range of 20-30 degrees
it is preferable to use a charge controller that compensates for the effect of
the battery temperature. It will adjust the controller settings to ensure that
charge and discharge cycles are modified based on temperature. The sensor
should be attached to or placed in the electrolyte of a battery in the middle
of the array to ensure that the actual battery temperature is measured instead
of the ambient temperature. The control algorithm of the charge controller can
be based on a SoC calculation or on voltage settings. It is preferable to use a
charge controller that protects the battery from a low state of charge by
calculating the SoC of the battery. The settings of the controller must be
chosen in accordance with the specifications of the battery manufacturer. If no
specification is given, typically a minimum SoC value of 70% for the common car
battery and 20% for batteries designed for deep discharge operation should be
used.
-
It is preferable to use a charge controller with separate voltage
sense-terminals. Otherwise the resistance of the cable between the battery and
the charge controller, in combination with the charge or discharge current, can
result in an incorrect voltage measurement.
-
It is essential to ensure that the charge controller has a means for selecting
the applied type of battery (i.e. vented or sealed) to ensure that the correct
charge regime is applied for battery type. This is especially important for
VRLA batteries since overcharging will dry out the battery electrolyte.