Recommendation: Category G4
Recommendations on category G4
Test procedure for category G4:
IEC61427 plus Qualibat (Combined test procedure, ageing ratio 1:1.5)
See Testprocedures and ref. [3])
As long as no results are available for this combined test procedure, select
the battery that has the best results (longest life time) for the two separate
test procedures.
Selection of battery and charge controller for category G4:
-
It is essential to use a charge controller that protects the battery from
overcharging. The recommended end-of-charge-settings of the controller depend
on the type of battery and the category of battery usage. The recommended
batteries are given below, in order of preference, together with the
recommended voltage settings for the charge controllers at charging.
Recommended battery
in order of preference |
Controller settings(in V/cell at 25°C) |
maint.
months |
Flooded, tubular plate
with electrolyte mixing |
Charge: 2.4 V(
2h / day)
Float 2.35 V
equalisation: 2.55 V (8h / 2 weeks) |
6 |
VRLA, tubular plate
with electrolyte mixing |
Charge: 2.45 V (2h / day)
Float 2.35 V
equalisation: 2.5 V (10h / month) |
6 |
-
It is essential to use a charge controller that protects the battery from deep
discharging. The control algorithm of the charge controller can be based on a
SoC calculation or on voltage settings. The recommended
end-of-discharge-settings of the controller are the following:
-
Low voltage Disconnect, for discharge current I10: 1.80 to 1.85 V/cell
-
Low voltage Disconnect, for discharge current 10% of I10: 1.95 to 2.0 V/cell
-
If the battery will be operated outside the temperature range of 20-30 degrees
it is preferable to use a charge controller that compensates for the effect of
the battery temperature. It will typically adjust settings to ensure that
charge and discharge cycles are modified based on temperature and voltage or
state of charge. A separate battery temperature sensor should be used.
-
It is preferable to use a charge controller with separate voltage sense
terminals.
-
In a system with a high charge factor and a long average time between full
charge, one can consider to replace part of the storage capacity with a back up
generator.
More specific recommendations for category G4:
The main battery issues of category G4 are operation at low state of charge,
long time between full charge and high partial cycling intensity despite a high
charge factor. Such conditions can only exist, if there are distinct
differences in operation, e.g. a very high charge factor when the battery is
full anyway and very poor operating conditions with cycling at low state of
charge and infrequent full charge. To improve battery performance, both
conditions have to be addressed.
To improve the low state of charge situation:
-
Apply the recommended values for the setpoints of the charge controller in the
table above.
-
Use a charge controller with a low self-consumption and with a high efficiency.
-
Reduce the load (e.g. by replacing appliances by more efficient ones).
For flooded batteries with a charge factor of intensity level 5 and VRLA
batteries with a charge factor of 4 or 5 measures should be taken to reduce the
charge factor such as:
-
Optimise the orientation (tilt and azimuth) of the PV-module for the period of
low irradiance (e.g. winter).
-
If a backup-generator is installed, consider reducing its operating time and
making sure that the generator is not operated in the morning to increase the
state of charge of the battery. PV production during the day will then likely
lead to this considerable overcharging.
Particularly in a high temperature environment there should be concern about the
battery thermal protection. The battery thermal control management particularly
of the auxiliary cooling system may be necessary due to the high charge factor
possibly leading to an overcharge requiring an extensive heat dissipation.
Attention should be paid also to low environmental conditions that would
require thermal protection against the electrolyte freeze.