Recommendation: Category G3
Recommendations on category G3
Test procedure for category G3:
IEC61427 plus Qualibat (Combined test procedure, ageing ratio 1:0.3)
See Testprocedures and ref. [3]).
As long as no results are available for this combined test procedure, select
the battery that has the best results (longest life time) for the two separate
test procedures.
Selection of battery and charge controller for category G3:
-
It is essential to use a charge controller that protects the battery from
overcharging. The recommended end-of-charge-settings of the controller depend
on the type of battery and the category of battery usage. The recommended
batteries are given below, in order of preference, together with the
recommended voltage settings for the charge controllers at charging.
Recommended battery
in order of preference |
Controller settings
(in V/cell at 25°C) |
maint.
months |
Flooded, Industrial,
thick flat plates,
large electrolyte reservoir |
Charge: 2.4 V (
2h / day)
Float 2.3 V
equalisation: 2.55 V (5h / 2 weeks)
|
1 |
Flooded, Industrial,
thick flat plates,
Automatic water topping |
Charge: 2.4 V (2h / day)
Float 2.3 V
equalisation: 2.55 V (5h / 2 weeks) |
6 |
-
It is essential to use a charge controller that protects the battery from deep
discharging. The control algorithm of the charge controller can be based on a
SoC calculation or on voltage settings. The recommended
end-of-discharge-settings of the controller are the following:
-
If the battery will be operated outside the temperature range of 20-30 degrees
it is preferable to use a charge controller that compensates for the effect of
the battery temperature. It will typically adjust settings to ensure that
charge and discharge cycles are modified based on temperature and voltage or
state of charge. A separate battery temperature sensor should be used.
-
It is preferable to use a charge controller with separate voltage sense
terminals.
More specific recommendations for category G3:
The main battery issue of category G3 is the high charge factor. For
flooded batteries the optimum is about 120% (intensity level 4) and
for VRLA batteries about 110% (intensity level 3). For flooded batteries with a
charge factor intensity of 5 and VRLA batteries with a charge factor intensity
of 4 or 5, measures should be taken to reduce the charge factor such as:
-
Apply the recommended values for the setpoints of the charge controller in the
table above.
-
Optimise the orientation (tilt and azimuth) of the PV-module for the period of
low irradiance (e.g winter).
-
Check whether the capacity of the renewable energy generator is not
unnecessarily high for the required loss-of load probability. This can also
lead to reduced investment costs.
-
4. If a backup-generator is installed, consider reducing its operating time and
making sure that the generator is not operated in the morning to increase the
state of charge of the battery. PV production during the day will then likely
lead to this considerable overcharging.